TORQUE RANGE |
TORQUE |
25 to 6,00,000 Nm for rotary and 1.2 to 8000 kN force for linear actuator |
ENCLOSURE PROTECTION |
Construction |
Casting: Cast Aluminium
Actuator: Refer DRS Series Actuator Catalouge |
Ingress Protection |
IP68 10m / 96h |
Controls location |
As standard, the controls are integral to the actuator
On option, the Controller can be mounted in a separated box
(maximum distance between actuator and controls = 50m) |
Explosion proof ATEX |
ATEX Directive 94/9/EC – CENELEC EN 60079-0, EN60079-1,EN13463
As standard: Ex d II B T4 (option T5 or T6) and Ex tb IIIC T135°C (option T100°C, T85°C)
On request: Ex d II C T4 (option T5 or T6) |
Explosion proof IEC Ex |
IEC Ex – standard IEC 60079-0, IEC60079-1, EN13463
As standard: Ex d II B T4 (option T5 or T6) and Ex tb IIIC
T135°C (option T100°C, T85°C)
On request: Ex d II C T4 (option T5 or T6) |
Ambient temperature operating range |
IIB standard: -20 … +70°C
IIB low temperature option: -60 … +70°C
IIC option: -20 … +70°C |
External corrosion protection |
Standard paint system: polyuréthane paint RAL3020
complying with ISO 12944 (C5)
Optional special anti-corrosion protection for marine,
aggressive or abrasive atmospheres
All cover fasteners captive and stainless |
Double sealing Protection |
The control section of the actuator is totally isolated from the terminal compartment to protect electronic components |
MOTOR |
Motor technology |
Single & three-phase TENV type, totally enclosed non
ventilated squirrel cage motors, Class F insulated with
Integral thermal overload protection
Class F insulated, DC motor with Integral thermal overload
protection
Easy to remove with sealed ball bearings fitted at front and
rear |
Motor duty rating |
S4 motor service (intermittent service on start-up) to IEC 34-1
S4 – 30% for On/Off operation – up to 360 starts per hour
S4 – 30% for Inching/Positioning – up to 360 starts per hour
S4 – 50% for Modulating class III – up to 1,200 starts per hour |
MECHANICAL SPECIFICATIONS |
Manual override |
Hydraulic Handpump |
Vibration Resistance |
1g (9.8 m/s²) at 10-500 Hz
(Contact our marketing dept. for higher vibration levels) |
Lubrication |
Actuators are lubricated for product lifetime and do not
require any specific periodic maintenance |
ELECTRICAL SPECIFICATIONS |
Power Supply |
The actuators can operate on a wide variety of power supplies:
Single-phase: 110, 120 & 230 V – 50/60 Hz
Three-phase: 380, 400, 415, 440, 480, 575, 690 V – 50/60 Hz
DC: 24V
Voltage tolerance: ±10%; Applies for rated torque
performance; duty cycle and speed is not guaranteed
Frequency tolerance: ±5%; Applies for rated torque
performance; duty cycle and speed is not guaranteed
Maximum starting volt drop: -15%; Actuators capable of
starting and running up to speed |
Cable Entries |
Standard configuration:
power & signal : 1”1/2 NPT + 2×1”NPT
fieldbus : up to 4×3/4”NPT
Other configurations available on request: plugs, adaptors, ISO thread |
Electrical connection |
Ring tongue terminals
Internal and external ground rod |
Fuse protection |
Primary fuse (6.3 x 32mm – 0.5 A) located on the transformer board
Two automatic fuses for low voltages |
POSITION AND PRESSURE SENSORS |
Position |
C ontactless sensor
Potentiometer (op tional) |
Pressure |
Pressure measured by piezoresistive pressure sensors based on ceramic |
CONTROLS |
Power circuit |
Integral motor reversing starters (electromagnetic contactors
for On-Off, Inching/Positioning, Modulating Class III) |
Display |
Back-lit graphics display with a choice of 9 different languages |
On-off remote Control (Hardwired Control) |
Command by
voltage: 10 to 250 V DC/AC (current: 10 mA at 24V)
dry contact (use Controller auxiliary 24 VDC supply) Isolated by opto-couplers
Minimum pulse duration: 100ms |
Signaling relays |
4 relays: each information can be freely selected
Contact configuration : normally open or normally closed
Minimum current 10mA at 5V
Maximum current 5A at 250V AC or 5A at 30VDC (resistive load)
Additional 3 relays board on option |
Fault relay |
Normally closed & energized SPDT contact
Minimum current 10mA at 5V
Maximum current 5A at 250V AC or 5A at 30V DC (resistive load) |
Analogue Control |
Input (setpoint) and output (feedback) signals are fully isolated from each other
Signal configurations (selectable):
Input signal: 4-20 mA – output signal: 4-20mA
Input signal: 0-20 mA – output signal: 0-20mA
Input signal: 0-10 V – output signal: 0-20mA (0-10V with an external resistance)
Analogue inputs:
in current: impedance of 160 Ohms
in voltage: impedance of 11 KOhms
Analogue outputs:
in current: maximum acceptable load of 750 Ohms at 24 VDC supply
In voltage: minimum acceptable load of 50 KOhms (with a shunt resistance of 500 Ohms) |
Transmitter (option) |
Proportional position (0/4-20 mA) and Pressure (4-20 mA) feedback board |
Limit Switches |
4 Mechanical Limit Switch (SPDT): 120/230 VAC or 30 VDC
Proximity Limit Switch NO/NC (Optional): 5-60 VDC |
Signaling continuity (option) |
Allows to use the display and update the open and closed position information (through the signaling relays
or Profibus DP) in case of lack of power supply |
Fire protection (option) |
30 minutes at 1,000°C
Tested to UL 1709 criteria |
SETTINGS |
Settings |
Non-Intrusive. All actuator settings and parameters are stored
in a non-volatile EEPROM memory. Protection
by password. Can be done by local command, infrared link or
optional bluetooth link (For a good safety level,
bluetooth link is limited at 10m) |
Local selectors |
The Controller can be fully set via its local display and selectors
Does not require any specific setting tool |
INTELLI+ KIT (option) |
INTELLI+ SOFT CD-ROM for laptop PC
Infrared module to connect to the laptop (USB) and clip on the actuator window
From update 3.00, INTELLI+ SOFT is also able to manage bluetooth link with advanced torque recordings |
INTELLI+ Pocket (option) |
Industrial pocket PC (PDA)
Protection: IP65 (option: ATEX II2G EEx ia IICT4)
Shock resistance: 1.2 m (on concrete)
Communication:
– with INTELLI+ : Infrared link (40 cm maximum distance)
– with PC: bluetooth, IRDA, Wifi (802.11b) as a standard
Optional USB station.
Operating system: Windows Mobile 2005, 64Mb RAM + 256Mb storage card |
FIELDBUS CONTROLS |
Profibus DPV1 (option) |
PROFIBUS-DPV1 – RS 485
Baud rate: 9.6 kbit/s up to 1.5 Mbit/s (autodetection)
Communication protocol: PROFIBUS DPV1 slave-cyclic & acyclic
Type of connection: single line (standard) or redundant line (option)
Cable specification: Profibus certified cable only
Line connection without repeater
Actuators per line: 31 max
Line length: 1.2 km max. (0.75 mi)
Line connection with repeaters
Number of repeaters per line: 9 max
30 actuators and 1 Km max. per segment
Number of actuators per line with repeater: 124 maximum
Line length with 9 repeaters: 10.2 km max. (6.2 mi)
Scan speed (30 units & 1.2 km): 0.1s (at a baud rate of 93.75 Kbit/s)
Power supply: internal and isolated via INTELLI+®.
Optional signaling battery or 24VDC external backup supply
update the open and closed position information in case of
loss of power supply
Technical approval: operability approved by PNO (Profibus
Nutzer Organisation) |
FIELDBUS CONTROLS |
Modbus (option) |
MODBUS RTU – RS 485
Transmission medium: 1 shielded pair cable
Functions: Half Duplex, asynchronous mode, multidrop
Baud rate: 1.2k to 115 Kbit/s
Format: 8 data bits, 1 stop bit, no parity
Communication protocol: Modbus (slave)
Modbus address: configurable by the actuator menu |
Foundation Fieldbus (option) |
H1 speed = 31.25kBit/s
Fully compliant with fieldbus standard IEC 61158
Physical layer: IEC 61158-2, 2 wires communication
Current consumption: 20mA
Operating voltage: 9 to 32 VDC
Cable specification: Type A (for example: 3076F Belden)
Line connection
Actuators per line without repeater: 31 max.
Line length without repeater: 1.9 km max. (1.2 mi)
Number of repeaters per line: 4 max.
Maximum number of actuators and line length depends on consumption available
Technical approval: Foundation tested. Several DCS manufacturer operability checked. |
Hart (option) |
Interface: HART, 4-20mA current, FSK modulation
Transfer speed: 1.2 kbit/s
Protocol: HART 7.4
Impedance: 250 Ohms
Power consumption: Internal by Intelli+ transformer, External
power supply for 4-20mA loop only
Actuator configuration: Available through EDD file
Connection line: Point-to-Point or Multi-drop
Technical approval: approved by Hart Communication Foundation |